Choose your country or region.

Image may be representation.
See specs for product details.

0902441

Manufacturer Part Number:
0902441
Manufacturer / Brand
Phoenix Contact
Part of Description:
CIR BRKR THRM-MAG 50A 480VAC
Datasheets:
0902441(1).pdf0902441(2).pdf
Lead Free Status / RoHS Status:
RoHS Compliant
Stock Condition:
New original, 47374 pcs Stock Available.
ECAD Model:
Ship From:
Hong Kong
Shipment Way:
DHL/Fedex/TNT/UPS

Inquiry Online

Please complete all required fields with your contact information.Click "SUBMIT REQUEST" we will contact you shortly by email. Or Email us: Info@IC-Components.com
Part Number
Manufacturer
Require Quantity
Target Price(USD)
Company Name
Contact Name
E-mail
Phone
Message
Please enter Verify Code and click "Submit"
Part Number 0902441
Manufacturer / Brand Phoenix Contact
Stock Quantity 47374 pcs Stock
Category Circuit Protection > Circuit Breakers
Description CIR BRKR THRM-MAG 50A 480VAC
Lead Free Status / RoHS Status: RoHS Compliant
Voltage Rating - AC 480 V
Series TMC 60
Package Bulk
Number of Poles 3
Mounting Type DIN Rail
Illumination Voltage (Nominal) -
Illumination -
Current Rating (Amps) 50A
Breaker Type Thermal Magnetic
Actuator Type Lever

Packaging & ESD

Industry-standard static shielding packaging is used for electronic components.Anti-static, light-transparent materials allow easy identification of ICs and PCB assemblies.
The packaging structure provides electrostatic protection based on Faraday cage principles.This helps protect sensitive components from static discharge during handling and transportation.


All products are packed in ESD-safe anti-static packaging. Outer packaging labels include part number, brand, and quantity for clear identification. Goods are inspected prior to shipment to ensure proper condition and authenticity.

ESD protection is maintained throughout packing, handling, and global transportation. Secure packaging provides reliable sealing and resistance during transit. Additional cushioning materials are applied when required to protect sensitive components.

QC(Part Testing by IC Components)Quality Warranty

We can offer worldwide express delivery service, such as DHLor FedEx or TNT or UPS or other forwarder for shipment.

Global Shipment by DHL/FedEx/TNT/UPS

Shipping Fees reference DHL/FedEx
1). You can offer your express delivery account for shipment, ifyou haven’t any express account for shipment, we can offer our account inadvance.
2). Use our account for shipment, Shipment charges(Reference DHL/FedEx, Different Countries has different price.)
Shipment charges: (Reference DHL and FedEX)
Weight(KG): 0.00kg-1.00kg Price(USD$) : USD$60.00
Weight(KG): 1.00kg-2.00kg Price(USD$) : USD$80.00
* The price of cost is reference with DHL/FedEx. The detail charges, please contact us. Different country the express charges are different.



We accept the payment terms: Telegraphic Transfer(T/T), Credit Card, PayPal and Western Union.

PayPal:

PayPal Bank Information:
Company Name : IC COMPONENTS LTD
Paypal ID: PayPal@IC-Components.com

BANK TRANSFAR (Telegraphic Transfer)

Payment For Telegraphic Transfers:
Company Name : IC COMPONENTS LTD Beneficiary Account Number : 549-100669-701
Beneficiary Bank name : Bank of Communications (Hong Kong) Ltd Beneficiary Bank Code : 382 (for local payment)
Beneficiary Bank SWIFT : COMMHKHK
Beneficiary Bank Address : Tsuen Wan Market Street Branch 53 Market Street, Tsuen Wan N.T., Hong Kong

Any inquires or questions, please kindly contact us Email: Info@IC-Components.com


Frequently Asked Questions

For Phoenix Contact 0902441, can I use this 3-pole 50A thermal-magnetic breaker on a 3-phase motor feeder with high inrush current?
Yes, Phoenix Contact 0902441 is commonly suited for 3-phase motor feeder protection where starting current is higher than the running current. Its thermal-magnetic trip behavior gives time-delay response to moderate overloads and faster magnetic response for short-circuits. For motor loads, the key design check is coordination with the motor starter, expected inrush profile, and downstream cable ampacity. If the motor has very frequent starts or unusually high locked-rotor current, the trip curve should be reviewed against the application profile to avoid nuisance tripping.
Can Phoenix Contact 0902441 be used as a feeder disconnect in a 480 VAC panel, or do I need a separate isolator?
Phoenix Contact 0902441 is often used as branch or feeder protection in 480 VAC control panels, but whether it can serve as the only disconnect depends on local code and the required isolation function. The breaker provides overcurrent protection and manual switching via the lever, yet some systems still require a dedicated disconnect switch with visible isolation or lockout provisions. In retrofit designs, engineers typically confirm short-circuit rating, upstream protective coordination, and the panel’s lockout/tagout strategy before using Phoenix Contact 0902441 as the sole disconnecting means.
Is Phoenix Contact 0902441 suitable for replacing an older thermal-magnetic breaker with the same 50A rating?
Phoenix Contact 0902441 can be a practical replacement when the existing breaker is also a 3-pole 50A device for DIN rail installation, but the electrical rating match alone is not enough. The replacement should be checked for pole spacing, terminal compatibility, DIN rail footprint, trip characteristic, and interrupting capacity relative to the system fault level. Even when the nameplate current is the same, differences in trip behavior can affect motor start-up, transformer energization, and nuisance-trip risk.
What should I verify before substituting Phoenix Contact 0902441 for part number 1020033?
Before substituting Phoenix Contact 0902441 for 1020033, compare the full application envelope rather than only the current rating. Engineers usually check frame size, mounting style, pole configuration, trip curve, terminal arrangement, and any differences in electrical endurance or short-circuit coordination. If 1020033 is being used in a circuit with sensitive downstream electronics, a small change in magnetic trip behavior can change how the protection system reacts during fault or inrush events.
Can Phoenix Contact 0902441 be used in circuits with both AC and DC operation?
Phoenix Contact 0902441 is described with a 480 V AC / DC rating, so it may be used in either AC or DC applications within the allowed design limits. In practice, DC use needs extra attention because arc interruption is more demanding on breakers than AC interruption. Engineers should confirm the actual DC voltage, polarity conditions if applicable, expected fault current, and the manufacturer’s DC derating or connection rules for the specific installation.
How do I know if Phoenix Contact 0902441 is appropriate for a panel that runs near 50A continuously?
Phoenix Contact 0902441 can be used near its rated current, but continuous loading should be evaluated against enclosure temperature, conductor sizing, terminal heating, and the installation’s duty cycle. Thermal-magnetic breakers can run warmer in tightly packed panels or elevated ambient conditions, which may reduce margin before thermal trip. For sustained high-load circuits, engineers often check derating guidance, wire size, and ventilation to avoid unintended trips during normal operation.
What design checks are needed when mounting Phoenix Contact 0902441 on a DIN rail next to other breakers?
When installing Phoenix Contact 0902441 on a DIN rail alongside other breakers, spacing, heat accumulation, and wiring access are the main checks. Adjacent devices can increase ambient temperature around the breaker, which affects thermal trip performance. It is also useful to verify terminal access for torqueing and conductor routing so that large-gauge conductors do not mechanically stress the lever or neighboring devices.
Is Phoenix Contact 0902441 suitable for industrial equipment that experiences vibration or long operating hours?
Phoenix Contact 0902441 is a DIN rail thermal-magnetic breaker intended for industrial control environments, so it is commonly used in equipment with continuous operation. For vibration-prone installations, the mounting integrity, rail quality, conductor support, and cabinet layout matter as much as the breaker itself. Over time, thermal cycling and repeated load changes can loosen terminations if wiring practices are not controlled, so periodic inspection of terminal torque and enclosure condition is advisable.
What are the practical differences between Phoenix Contact 0902441 and a fuse-based protection approach?
Phoenix Contact 0902441 offers resettable protection and manual switching, while fuses typically provide simpler fault clearing and very high interrupting performance depending on type. In maintenance-heavy systems, a breaker can reduce downtime because it can be reset after investigating the fault. In extremely high fault-current applications, however, engineers may still choose fuses or coordinate the breaker with upstream protection to achieve the required fault-clearing behavior and let-through energy control.
Can Phoenix Contact 0902441 be used for transformer primary protection?
Phoenix Contact 0902441 may be usable on transformer primary circuits if the inrush current, primary current, and short-circuit level are all within the breaker’s operating range. Transformer magnetizing inrush can momentarily be much higher than normal load current, so nuisance tripping is a common concern. Designers usually compare the transformer inrush profile with the breaker’s thermal-magnetic characteristics and confirm that the upstream and downstream devices coordinate properly.
How should I decide whether Phoenix Contact 0902441 is the right breaker for a replacement panel rebuild?
For a panel rebuild, Phoenix Contact 0902441 is a good fit when the original design needs a 3-pole 50A thermal-magnetic breaker on DIN rail and the system voltage is within the 480 V AC/DC class. The decision usually comes down to whether the existing conductor sizes, load type, and fault ratings remain unchanged. If the old panel used a different trip behavior or a different mechanical form factor, the engineer should verify that the new device preserves operational behavior and does not force a wiring or enclosure redesign.
What operating conditions can reduce the service life or stability of Phoenix Contact 0902441 in the field?
For Phoenix Contact 0902441, elevated ambient temperature, repeated near-trip loading, poor terminal torque, and panel contamination can all affect long-term stability. Thermal-magnetic breakers respond to temperature, so a hot enclosure can shift the effective trip point compared with a cooler lab environment. In industrial use, it is common to review cabinet airflow, conductor sizing, and maintenance intervals to keep the breaker operating consistently over time.

Recent Reviews

Leave Comment
Hello, you have not logged in, please log in
User Login

Forgot password?

No account yet? Register now

Tips
Please speak legally
Your email will be hidden
Please complete all required fields ( denoted with* )
Mark
5.0

You May Also Be Interested In:


0902441

Phoenix Contact

CIR BRKR THRM-MAG 50A 480VAC

In Stock: 47374

SUBMIT RFQ